AUP- 1003-TSB

Aurora AUP- 1003-TSB Uninterruptible Power Supply

  • High power density
  • Input power factor 0.99 with PFC
  • Maximum charging current can be expanded to 12A (Long run unit)
  • Intelligent fans peed regulation
  • Multiple communication interface: RS232 (USB/EPO/Relay card /SNMP card)
  • Multiple protection function: short-circuit, overload, overheat, battery overcharge and over discharge, output low voltage and fan fault alarm

Specifications


SPECIFICATIONS
Capacity 3000VA/2700W
Frequency Frequency range: 40〜70Hz (50/60Hz Auto-Sensing)
Input
  • Nominal voltage: 208/220/230/240Vac
  • Input voltage range: 110〜300Vac (176〜264Vac @
  • 100% load)
  • Power factor: ≥0.99
Output
  • Output voltage: 208/220/230/240Vac
  • Voltage regulation: ±1%
  • Power factor: 0.9
  • Output frequency: Line mode: 46〜54Hz or 56~64Hz, Bat. mode: (50/60±0.1%)Hz
  • Crest factor: 3:1
  • Harmonic distortion (THDv): ≤3% Linear load, ≤5% Non linear load
  • Transfer time: AC mode to Bat.mode: 0ms, Inverter to Bypass: 4ms (Typical)
  • Output waveform: Pure Sinewave
Efficiency
  • AC mode: 91%
  • Battery mode: 88%
Battery
  • Battery number : 6
  • Capacity (Standard unit): 9Ah/12V (7Ah/12V optional)
  • Typical recharging time: 4 hours (To 90% of full
  • capacity)
  • Charging current (Max.): 1A
Alarm
  • Battery mode: Beeping every 4 seconds
  • Battery low: Beeping every second
  • Overload: Beeping twice every second
  • Fault: Continuously beeping
Indicators
  • LED display: Line mode, Bat.mode, ECO mode, Bypass mode, Battery low voltage, Overload & UPS fault
  • LCD display: Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature& Remaining battery backup time
Physical
  • Dimension W×D×H: 191×460×337mm
  • Net weight: 29.5kg
Standards
  • Safety: IEC/EN 62040-1, IEC/EN 62477-1
  • EMC: IEC/EN 62040-2 (IEC 61000-4-2, IEC 61000 4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11, IEC 61000-2-2)
Environment
  • Operating temperature: 0℃~40℃
  • Storage temperature: −25℃~55℃
  • Humidity range: 20~95%RH @ 0~40℃ (Noncondensing)
  • Altitude: <1500m, derating required when>1500m
  • Noise level: <50dB at 1 Meter

Documentations

Please download the technical documents here