SPECIFICATIONS |
|
Capacity |
3000VA/2700W |
Frequency |
Frequency range: 40〜70Hz (50/60Hz Auto-Sensing) |
Input |
- Nominal voltage: 208/220/230/240Vac
- Input voltage range: 110〜300Vac (176〜264Vac @
- 100% load)
- Power factor: ≥0.99
|
Output |
- Output voltage: 208/220/230/240Vac
- Voltage regulation: ±1%
- Power factor: 0.9
- Output frequency: Line mode: 46〜54Hz or 56~64Hz, Bat. mode: (50/60±0.1%)Hz
- Crest factor: 3:1
- Harmonic distortion (THDv): ≤3% Linear load, ≤5% Non linear load
- Transfer time: AC mode to Bat.mode: 0ms, Inverter to Bypass: 4ms (Typical)
- Output waveform: Pure Sinewave
|
Efficiency |
- AC mode: 91%
- Battery mode: 88%
|
Battery |
- Battery number : 6
- Capacity (Standard unit): 9Ah/12V (7Ah/12V optional)
- Typical recharging time: 4 hours (To 90% of full
- capacity)
- Charging current (Max.): 1A
|
Alarm |
- Battery mode: Beeping every 4 seconds
- Battery low: Beeping every second
- Overload: Beeping twice every second
- Fault: Continuously beeping
|
Indicators |
- LED display: Line mode, Bat.mode, ECO mode, Bypass mode, Battery low voltage, Overload & UPS fault
- LCD display: Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature& Remaining battery backup time
|
Physical |
- Dimension W×D×H: 191×460×337mm
- Net weight: 29.5kg
|
Standards |
- Safety: IEC/EN 62040-1, IEC/EN 62477-1
- EMC: IEC/EN 62040-2 (IEC 61000-4-2, IEC 61000 4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11, IEC 61000-2-2)
|
Environment |
- Operating temperature: 0℃~40℃
- Storage temperature: −25℃~55℃
- Humidity range: 20~95%RH @ 0~40℃ (Noncondensing)
- Altitude: <1500m, derating required when>1500m